ba76034e01 01/2012IQ SENSOR NETMIQ/IC2Operating ManualPower!OKIQ SENSOR NET Current input module2 x 0/4 ... 20 mAwith power supply/isolator feed-in
Installation MIQ/IC23 - 2ba76034e01 01/2012 Any wires that are not used and project into the housing must be cut off as closely as possible to the ca
MIQ/IC2 Installation3 - 3ba76034e01 01/2012NoteNo free wires must be allowed to project into the housing. Otherwise there is the risk of malfunction.
Installation MIQ/IC23 - 4ba76034e01 01/20123.4 Installation examplesThe following installation examples demonstrate the basic application of the MIQ/I
MIQ/IC2 Installation3 - 5ba76034e01 01/2012Connecting externalmeters via a power sup-ply/isolatorThe current outputs of external meters can be directl
Installation MIQ/IC23 - 6ba76034e01 01/2012
MIQ/IC2 Settings4 - 1ba76034e01 01/20124 SettingsOverview The MIQ/IC2 module provides two 0/4 ... 20 mA current inputs for the IQ SENSOR NET. Each cur
Settings MIQ/IC24 - 2ba76034e01 01/2012Settings The following settings can be made for the sensor (default settings are marked in bold):Display indica
MIQ/IC2 Settings4 - 3ba76034e01 01/2012Fig. 4-3 Measuring range: 4 ... 20 mA, Error detection >= Error threshold (IF);IF = 20.5 mAFig. 4-4 Measurin
Settings MIQ/IC24 - 4ba76034e01 01/2012Fig. 4-5 140 - Settings of sensors and diff. sensorsFig. 4-6 140 - Settings of sensors and diff. sensors5 Confi
MIQ/IC2 What to do if ...5 - 1ba76034e01 01/20125 What to do if ...No measured value Measurement providesimplausible measuredvaluesDisplay of OFLCause
MIQ/IC22ba76034e01 01/2012NoteFor the most recent version of the manual, please visit www.ysi.com.Contact YSI1725 Brannum LaneYellow Springs, OH 45387
What to do if ... MIQ/IC25 - 2ba76034e01 01/2012
MIQ/IC2 Maintenance and cleaning6 - 1ba76034e01 01/20126 Maintenance and cleaning6.1 MaintenanceThe MIQ/IC2 requires no special maintenance. The gener
Maintenance and cleaning MIQ/IC26 - 2ba76034e01 01/2012
MIQ/IC2 Technical data7 - 1ba76034e01 01/20127 Technical dataNoteGeneral technical data on MIQ modules are given in the TECHNICAL DATA chapter of the
Technical data MIQ/IC27 - 2ba76034e01 01/2012Current inputsFeed-in(power supply/isolator)Measuring channels 2Physically separated from the IQ SENSOR N
MIQ/IC2 Contact Information8 - 1ba76034e01 01/20128 Contact Information8.1 Ordering & Technical SupportWhen placing an order please have the follo
Contact Information MIQ/IC28 - 2ba76034e01 01/2012
MIQ/IC2 Lists9 - 1ba76034e01 01/20129Lists9.1 Explanation of the messagesIn this chapter you will find a list with all the message codes and corre-spo
Lists MIQ/IC29 - 2ba76034e01 01/20129.1.2 Informative messagesThe MIQ/IC2 current input module does not send any info messages.9.2 Status infoThe stat
MIQ/IC2 List of contents0 - 1ba76034e01 01/2012MIQ/IC2 - List of contents1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1725 Brannum LaneYellow Springs, Ohio 45387 USA+1 937-767-7241800-765-4974 (US)FAX (937) 767-1058Email: [email protected]: www.ysi.com
List of contents MIQ/IC20 - 2ba76034e01 01/2012
MIQ/IC2 Overview1 - 1ba76034e01 01/20121Overview1.1 How to use this component operating manualStructure of theIQ SENSOR NEToperating manualFig. 1-1 St
Overview MIQ/IC21 - 2ba76034e01 01/20121.2 Features of the MIQ/IC2General characteristics The MIQ/IC2 current input module provides two 0/4 ... 20 mA
MIQ/IC2 Safety instructions2 - 1ba76034e01 01/20122 Safety instructionsThis operating manual contains special instructions that must be followed durin
Safety instructions MIQ/IC22 - 2ba76034e01 01/20122.1 Authorized useThe authorized use of the MIQ/IC2 consists of the provision of two 0/4 ... 20 mA c
MIQ/IC2 Installation3 - 1ba76034e01 01/20123 Installation3.1 Scope of deliveryThe scope of delivery of the MIQ/IC2 is listed in the INSTALLATION chapt